作者(zhe): 更新(xin)時間:2020-07-30弱(ruo)(ruo)(ruo)電(dian)工(gong)程是電(dian)力(li)運用的一個歸類,電(dian)力(li)運用依(yi)照電(dian)力(li)運輸(shu)輸(shu)出功(gong)率的高低能(neng)夠 分成弱(ruo)(ruo)(ruo)電(dian)與弱(ruo)(ruo)(ruo)電(dian)安裝(zhuang)兩大(da)類。工(gong)程建筑(zhu)及古建筑(zhu)群用電(dian)一般指溝(gou)通(tong)交流380V50Hz及下列的弱(ruo)(ruo)(ruo)電(dian)安裝(zhuang),關鍵向大(da)家出示(shi)電(dian)力(li)能(neng)源,將電(dian)磁能(neng)變換為別的電(dian)力(li)能(neng)源,比如中央空調用電(dian),照明燈具(ju)用電(dian),驅(qu)動力(li)用電(dian)這些。綜合布線系統(tong)(tong)范疇很廣(guang),在其中與智能(neng)安防有關的系統(tong)(tong)軟件有:保安人員視頻監控(kong)(kong)系統(tong)(tong)、消防安全報警設(she)備、進出口(kou)自動控(kong)(kong)制系統(tong)(tong)、停車收費智能(neng)管(guan)理系統(tong)(tong)和樓宇自控(kong)(kong)系統(tong)(tong)軟件,弱(ruo)(ruo)(ruo)電(dian)安裝(zhuang)安裝(zhuang)在安防中起著至關重要的功(gong)效。
一、 施工步驟:
1、勘察現場
與(yu)客戶協(xie)商,借用存放材料的材料間,材料間要足夠大,且距離施工現場較近。
水電(dian)設備。現場是否具備施(shi)工必需(xu)的水電(dian)設施(shi)。
電力負荷(he)(he)。施工現場的(de)(de)電力線是否(fou)能(neng)匹配工程的(de)(de)負荷(he)(he)要求。
設(she)備(bei)布(bu)局。確定機柜的位(wei)置、終端設(she)備(bei)的安裝(zhuang)位(wei)置以及線路的的敷設(she)路逕。
樣(yang)品(pin)式(shi)樣(yang)。明確客戶(hu)的要求,確定樣(yang)品(pin)的型(xing)號(hao)、樣(yang)式(shi)。要形(xing)成文檔,客戶(hu)簽字確認(ren)。
安(an)全。原材料的(de)安(an)全,施工現(xian)場的(de)防(fang)火防(fang)盜的(de)措施。
2、繪(hui)制網絡拓撲圖、布局圖,交客戶(hu)方確認。
3、制定(ding)工(gong)(gong)程進度(du)計(ji)劃(hua)表。列舉施工(gong)(gong)期間(jian)需要(yao)完成的工(gong)(gong)作任(ren)務,以及各(ge)項工(gong)(gong)作完成的先后次序,并確定(ding)詳(xiang)細的計(ji)劃(hua)時間(jian),如下圖所示。工(gong)(gong)程進度(du)表完成后需交(jiao)給客戶一份(fen),以備客戶監督(du)和(he)配(pei)合。
4、指(zhi)定工程負責(ze)人和(he)工程監(jian)理人員,負責(ze)規劃備(bei)料,備(bei)工,用(yong)戶方配合(he)要求等方面(mian)事(shi)宜,提出各部門配合(he)的時間表,負責(ze)內外協調和(he)施工組織(zhi)和(he)管理。
5、現場施工,每日記錄施工進(jin)度,并根據計劃的(de)完成情況(kuang)及時調整計劃,確保按工期(qi)工要求交付(fu)工程(cheng)。
6、現場認證測(ce)試(shi),制作測(ce)試(shi)報告,打印IP地址(zhi)表(biao)、路(lu)由表(biao)、配置表(biao)。
7、驗收。在上(shang)述(shu)各(ge)環節中所建立和完(wan)善的文(wen)檔,作為(wei)驗收資(zi)料的一部分,交(jiao)客戶保存。同時公司也要(yao)留存幅本,作為(wei)客戶資(zi)料,以備售后(hou)服(fu)務用。
二、布局規范:
布(bu)局(ju)是后(hou)續(xu)工(gong)作的基礎,所(suo)以(yi)一定要(yao)事先確定下(xia)來,否則一旦返工(gong),代價極高。布(bu)局(ju)圖(tu)(tu)必段根據場地、設施實際盡尺寸,按比例繪制,圖(tu)(tu)中要(yao)標(biao)明詳細尺寸。確定好布(bu)局(ju)圖(tu)(tu)要(yao)給客(ke)戶簽字確認,必要(yao)時可在(zai)場地上勾(gou)描出布(bu)局(ju)的輪廓以(yi)獲得直觀感受。
三、布線規范(網線、電源線)
1、電纜標志內容:在(zai)電(dian)纜(lan)的(de)護套(tao)上約(yue)以1M的(de)間隔標明(ming)生產(chan)廠廠名或(huo)代(dai)號(hao)及電(dian)纜(lan)型號(hao)規(gui)格,制造年份,電(dian)纜(lan)長度(du)。
2、塑料線(xian)槽及其(qi)附(fu)件型號(hao)規格應(ying)符合(he)設(she)計(ji)要(yao)求(qiu),并選(xuan)用相應(ying)的定(ding)型產品。其(qi)敷設(she)場所的環境溫度不(bu)得低于-15攝(she)氏度,其(qi)阻(zu)燃性能氧指數(shu)不(bu)應(ying)低于27%。線(xian)槽內外應(ying)光滑無(wu)棱刺,不(bu)應(ying)有(you)有(you)扭曲、翹邊等變形現(xian)象(xiang),并有(you)產品合(he)格證。
3、纜線(xian)布(bu)放時應有冗(rong)余。在機柜處,雙絞線(xian)纜預(yu)留長(chang)度,一般為(wei)3~6m;終端處為(wei)0.3~0.6m;光纜在設(she)備端預(yu)留長(chang)度一般為(wei)5~10m;有特(te)殊(shu)要(yao)求的(de)應按設(she)計要(yao)求預(yu)留長(chang)度
4、設備間鋪設活(huo)動地(di)板時(shi),板塊鋪設嚴(yan)密堅固,每平(ping)方米水平(ping)允(yun)許偏差不應大(da)于2mm,地(di)板支柱牢固,活(huo)動地(di)板防靜電措施的接地(di)應符合設計(ji)和產品說明要求。
5、每對對絞(jiao)(jiao)線應盡量保持扭絞(jiao)(jiao)狀(zhuang)態(tai),非扭絞(jiao)(jiao)長度(du)不(bu)應大于13mm。
6、剝除(chu)護套(tao)均不得刮(gua)傷絕緣層,應使(shi)用專用工具剝除(chu)。
7、纜線中(zhong)間不得產(chan)生接頭(tou)現象。
8、雙(shuang)絞線(xian)較長線(xian)距為(wei)100米(mi),超過100 米(mi)的可用雙(shuang)絞線(xian)中(zhong)繼(ji)(ji)器(qi)(qi)連結加(jia)長,每段(duan)線(xian)路中(zhong)中(zhong)繼(ji)(ji)器(qi)(qi)的數據不能(neng)多于三個。
9、光(guang)纖傳(chuan)(chuan)輸(shu)距(ju)(ju)離:傳(chuan)(chuan)輸(shu)速率1Gb/s,850nm,、普通50μm多模光(guang)纖傳(chuan)(chuan)輸(shu)距(ju)(ju)離550m,普通62.5μm多模光(guang)纖傳(chuan)(chuan)輸(shu)距(ju)(ju)離275m,新型50μm多模光(guang)纖傳(chuan)(chuan)輸(shu)距(ju)(ju)離1100m。
10、纜(lan)線(xian)的(de)彎曲(qu)半徑應符(fu)合下(xia)列規(gui)定:
a 非屏蔽(bi)4對雙絞線纜的(de)彎曲半徑應至少為電纜外(wai)徑的(de)4倍在(zai)施工過(guo)程(cheng)中應至少為8倍。
b 屏(ping)蔽雙絞線(xian)纜(lan)的(de)彎曲(qu)半(ban)徑(jing)應(ying)至少為電纜(lan)外徑(jing)的(de)6~10倍。
c 主干雙絞(jiao)線(xian)纜的(de)彎曲半徑應至少(shao)為電纜外徑的(de)10倍(bei)。
d 光纜的彎(wan)曲半徑(jing)(jing)應至(zhi)少為(wei)光纜外徑(jing)(jing)的1.5倍,在(zai)施(shi)工過(guo)程中應至(zhi)少為(wei)20倍。
11、 對絞線在(zai)信(xin)息插(cha)座(RJ45)相連時(shi),必須按色(se)標(biao)和線對順序進行卡接(jie)。插(cha)座類型,色(se)標(biao)和編號(hao)應(ying)符T568A、T568B的規定。
12、在制(zhi)作水晶頭(tou)時,電纜(lan)(lan)的(de)(de)外保護層(ceng)需要壓在接(jie)(jie)頭(tou)中而不能在接(jie)(jie)頭(tou)外。因為當(dang)電纜(lan)(lan)受(shou)到外界的(de)(de)拉力時受(shou)力的(de)(de)是(shi)整個(ge)電纜(lan)(lan),否則受(shou)力的(de)(de)是(shi)電纜(lan)(lan)和接(jie)(jie)頭(tou)連接(jie)(jie)的(de)(de)金屬部分。
13、雙(shuang)絞線(xian)(xian)纜與接線(xian)(xian)模塊(IDC,RJ45)卡接時,應(ying)按設計和(he)廠(chang)家規定進(jin)行(xing)操作。
14、 屏蔽(bi)雙絞線纜的屏蔽(bi)層(ceng)與接(jie)插件終端處屏蔽(bi)罩(zhao)可靠接(jie)觸,纜線屏蔽(bi)層(ceng)應與接(jie)插件屏蔽(bi)罩(zhao)360o圓周接(jie)觸,接(jie)觸長度不宜小于100mm。
15、每股雙膠線兩端(duan)應粘膠標簽并編號(hao),以便(bian)于安裝和維護。
16、交接間、設備間提供可靠的(de)施工(gong)電源和接地裝置。
17、施(shi)工現場臨時電(dian)源應有(you)完(wan)整的(de)插頭(tou).開關.插座.漏電(dian)保護(hu)器(qi)設置,臨時用電(dian)須(xu)用電(dian)纜。電(dian)源線(xian)分三種顏色(se):火(huo)線(xian)紅色(se).零(ling)線(xian)蘭色(se).地線(xian)黃色(se).所有(you)單向插座應該“左(zuo)零(ling)右火(huo)中間地“或“上火(huo)下(xia)零(ling)“連接。
18、電(dian)源(yuan)線(xian)(xian)管從地面(mian)下(xia)穿過時(shi),必(bi)須使用套管連(lian)接(jie)緊密(mi),在(zai)地面(mian)下(xia)不允許有(you)接(jie)頭,出入地面(mian)處必(bi)須套用彎頭。地面(mian)沒有(you)封閉之前,必(bi)須保護好(hao)PVC套管,不允許有(you)破(po)裂損傷,鋪地板(ban)磚(zhuan)時(shi)PVC套管應被覆(fu)蓋,釘木(mu)地板(ban)時(shi),電(dian)源(yuan)線(xian)(xian)應沿墻角(jiao)鋪設(she),以防止電(dian)源(yuan)線(xian)(xian)被釘子損傷。
19、 電源線走向橫平(ping)豎直,不(bu)可斜拉,防止被電錘(chui).釘子損傷(shang)。
20、各種強弱(ruo)電插座接口要(yao)盡量少(shao)。所(suo)有插座.開(kai)關要(yao)高于(yu)地面(mian)300MM以上,并(bing)且不會被推拉門家俱等(deng)物遮(zhe)擋。
21、弱電線路(lu)(lu)與強電線路(lu)(lu)不允許共套一管(guan),其間隔距離為0.5m以上。
22、三相五線(xian)(xian)(xian)(xian)制是指A、B、C、N和PE線(xian)(xian)(xian)(xian),其中(zhong),PE線(xian)(xian)(xian)(xian)是保護地線(xian)(xian)(xian)(xian),也叫安(an)全線(xian)(xian)(xian)(xian),是專門用(yong)(yong)(yong)(yong)于(yu)接到諸(zhu)如(ru)設備外殼等保證用(yong)(yong)(yong)(yong)電安(an)全之用(yong)(yong)(yong)(yong)的(de)。應用(yong)(yong)(yong)(yong)中(zhong)建議(yi)使用(yong)(yong)(yong)(yong)標準/規范的(de)導線(xian)(xian)(xian)(xian)顏(yan)色:A線(xian)(xian)(xian)(xian)用(yong)(yong)(yong)(yong)黃***線(xian)(xian)(xian)(xian)用(yong)(yong)(yong)(yong)藍(lan)色,C線(xian)(xian)(xian)(xian)用(yong)(yong)(yong)(yong)紅色,N線(xian)(xian)(xian)(xian)用(yong)(yong)(yong)(yong)褐(he)色,PE線(xian)(xian)(xian)(xian)用(yong)(yong)(yong)(yong)黃綠色。
23、工(gong)程(cheng)中各板塊之間的(de)電源要(yao)盡量(liang)分開控制,盡量(liang)做到獨立(li)供(gong)電,互不干憂。
四、設備安裝與調試
1、機柜安放位置的選擇規范
A .安(an)全性(xing)。隱(yin)蔽,通風,建議有(you)專用間,進出有(you)限制。B.可靠性(xing)。有(you)合適的(de)電源接入(ru)點(dian),有(you)足夠的(de)電力保障,維(wei)護方便。C.可用性(xing)。到(dao)各終端(duan)的(de)線(xian)距在規范要求的(de)范圍以內。D.經濟性(xing)。到(dao)終端(duan)線(xian)距總量較(jiao)小。
2、網絡設備的安裝規范
A.網(wang)絡設備(路由(you)器、交(jiao)換機等)應安裝(zhuang)在固定(ding)的托架上;
B.固定的托架一般應距地面500mm以上;
C.插入(ru)網絡設備的電纜線要固(gu)定在(zai)托(tuo)架或墻上,防止意外脫落。
3、終端設備安裝步驟
A.首先閱讀設備手冊和設備安裝說明書。
B.設(she)備(bei)開箱(xiang)要按裝箱(xiang)單進(jin)行清點,對設(she)備(bei)外觀進(jin)行檢查,認真詳細地做好記錄。
C.設備就位。
D.逐臺設備分(fen)別進行加電,做好(hao)自檢。
E.逐臺(tai)設備分別(bie)聯(lian)到服務器上(shang),進行聯(lian)機(ji)檢查,出現問題應(ying)逐一解決(jue)。有故障(zhang)的設備留在然后解決(jue)。
F.安裝系(xi)統(tong)軟件,進行主系(xi)統(tong)的聯調工作。
G.安(an)裝各(ge)工作(zuo)站(zhan)軟件,各(ge)工作(zuo)站(zhan)可正常上(shang)網工作(zuo)。
H.逐個解決遺留的所有問(wen)題。
I.用戶按操作規程(cheng)可(ke)任意(yi)上機檢查,熟悉(xi)網絡系統的各(ge)種功能。
J.試運行開始。
五、弱電工程故障排查規范
1、根據統計,弱電(dian)工程故(gu)障大(da)約50%一70%與電(dian)纜有(you)關系。所以電(dian)纜本身的質量(liang)以及安裝質量(liang)都直接(jie)影響網絡的正常運行(xing)。網絡電(dian)纜故(gu)障有(you)很多種(zhong),概(gai)括起來可以分為物理故(gu)障(也可稱連接(jie)故(gu)障)和(he)電(dian)氣性(xing)能故(gu)障兩(liang)大(da)類。
A.物理(li)故(gu)障(zhang)。物理(li)故(gu)障(zhang)主要是(shi)(shi)指由(you)于(yu)主觀因素造成的可以直接觀察的故(gu)障(zhang),多是(shi)(shi)由(you)于(yu)施工的工藝(yi)或對網絡電纜的意外(wai)損傷(shang)所造成的,如:模塊、接頭的線序錯(cuo)誤(wu),鏈(lian)路(lu)的開路(lu)、短路(lu)、超長等。
B.電(dian)(dian)(dian)氣性(xing)能(neng)故障。電(dian)(dian)(dian)氣性(xing)能(neng)故障主(zhu)要(yao)是(shi)指(zhi)鏈路的(de)電(dian)(dian)(dian)氣性(xing)能(neng)指(zhi)標未(wei)達到(dao)測試(shi)標準的(de)要(yao)求,即電(dian)(dian)(dian)纜在信號傳輸過(guo)(guo)程(cheng)中達不(bu)到(dao)設計要(yao)求。影響電(dian)(dian)(dian)氣性(xing)能(neng)因素除電(dian)(dian)(dian)纜材料本(ben)身(shen)的(de)質量(liang)外,還(huan)包括(kuo)施工(gong)過(guo)(guo)程(cheng)中電(dian)(dian)(dian)纜的(de)過(guo)(guo)度(du)彎曲(qu)、電(dian)(dian)(dian)纜捆綁太緊(jin)、過(guo)(guo)力拉伸和過(guo)(guo)度(du)靠近(jin)干(gan)擾源(yuan)等,如:近(jin)端串(chuan)擾、衰減(jian)、回(hui)波損耗等。
2、綜合布(bu)線的(de)故障多在水平區(qu)。這里穿線和模塊(kuai)端(duan)接較多,施工工藝因人而(er)異,建筑格局比(bi)垂直部分復雜。總體(ti)來說引起故障有3方(fang)面。
A.產(chan)品本身的電氣性能(neng),即產(chan)品的設(she)計(ji)(ji)與生(sheng)產(chan)質(zhi)量(liang)。B.工程方案的設(she)計(ji)(ji),根據(ju)建(jian)筑(zhu)格局,對(dui)布(bu)線系統的設(she)計(ji)(ji)要求。C.施(shi)工工藝,這是布(bu)線整(zheng)體質(zhi)量(liang)的體現(xian),好(hao)(hao)(hao)的產(chan)品和好(hao)(hao)(hao)的施(shi)工方案,都要有好(hao)(hao)(hao)的施(shi)工完成。
3、打線(xian)的(de)常見錯誤(wu)。打線(xian)的(de)常見錯誤(wu)有(you)(you)開路,短路,反接(jie)(jie)(一對(dui)線(xian)中的(de)兩根交叉了,如(ru)(ru)1對(dui)應2,2對(dui)應1)。另外一個(ge)錯誤(wu)是跨接(jie)(jie),如(ru)(ru)1、2對(dui)應3、6。造成(cheng)這種錯誤(wu)的(de)原(yuan)因主要有(you)(you)兩個(ge)。一是電(dian)纜的(de)一端使用(yong)(yong)了T568A標準,而電(dian)纜的(de)另一端使用(yong)(yong)了T568B標準。二是在網絡(luo)的(de)實際應用(yong)(yong)中,有(you)(you)時(shi)需要使用(yong)(yong)這種跨接(jie)(jie)線(xian)。當有(you)(you)的(de)交換機與交換機進行級連時(shi)就需要使用(yong)(yong)跨接(jie)(jie)線(xian)。
另外(wai)當把PC機和PC機進行(xing)對(dui)接(jie)(jie)時(shi)(shi)(不通過交(jiao)(jiao)換機),也需(xu)要使(shi)(shi)用(yong)跨(kua)接(jie)(jie)線(xian)。有的(de)(de)用(yong)戶(hu)使(shi)(shi)用(yong)了跨(kua)接(jie)(jie)線(xian)時(shi)(shi)也可(ke)以(yi)上網,而使(shi)(shi)用(yong)正確接(jie)(jie)線(xian)時(shi)(shi)也能進行(xing)交(jiao)(jiao)換機的(de)(de)級連。這(zhe)是因為他們使(shi)(shi)用(yong)的(de)(de)交(jiao)(jiao)換機是智能交(jiao)(jiao)換機。這(zhe)種交(jiao)(jiao)換機可(ke)以(yi)自動將接(jie)(jie)線(xian)的(de)(de)繞對(dui)對(dui)調過來。但(dan)這(zhe)不代表這(zhe)種打線(xian)的(de)(de)方(fang)式是正確的(de)(de)。
然(ran)后(hou)還有一種(zhong)錯誤就是(shi)串(chuan)繞。通(tong)常(chang)(chang)造成(cheng)這(zhe)種(zhong)結果的(de)原(yuan)因(yin)是(shi)1、2為(wei)一對,3、4為(wei)一對,5、6為(wei)一對,7、8 為(wei)一對。而網絡進(jin)行(xing)通(tong)訊(xun)時(shi)使用(yong)1、2和3、6,而不(bu)是(shi)3、4。這(zhe)種(zhong)錯誤的(de)接(jie)線(xian)是(shi)無法用(yong)眼睛或萬用(yong)表來(lai)檢查(cha)出來(lai)的(de),因(yin)為(wei)其端(duan)至端(duan)的(de)連(lian)通(tong)性是(shi)正常(chang)(chang)的(de)。而這(zhe)種(zhong)錯誤接(jie)線(xian)的(de)較大危害是(shi)會產生(sheng)很大的(de)近端(duan)串(chuan)擾。它不(bu)會造成(cheng)網絡不(bu)通(tong),而是(shi)使網絡運行(xing)速度很慢(man),時(shi)通(tong)時(shi)斷。它屬于(yu)軟故障,當(dang)網絡運行(xing)后(hou)檢查(cha)起(qi)來(lai)很麻煩。
-